China OEM Prepayment system Suppliers –Silver Electrolytic Copper Expulsion Fuse – HolleyDetail:
Spezifikationen
Produkt Typ |
| EXPULSION FUSE CUT OUT, 27 kV, 150kVBIL, 100 A 8/12kA, 470mm Kriechstrecke | EXPULSION FUSE CUT OUT, 38kV, 170kVBIL, 100A, 5/8 kA, 660mm CREEPAGE DISTANCE | EXPULSION FUSE CUTOUT, 27kV, 150kVBIL, 200A, 7.1/10 kA, 432mm CREEPAGE DISTANCE | |
Nein. | Funktionen | Einheit | Wert | Wert | Wert |
1 | BASIS |
| |||
| Modell | HV1-27/100-8 | HV1-38/100-5 | HV1-27/200-7.1 | ||
| Standard | ANSI/IEEE C 37.40/41/42 IEC60282- 2:2008 | ANSI C-37.40/41/42 and IEC60282-2 | ANSI/IEEE C37.40/41/42 y IEC60282-2:2008 | ||
| Nennstrom | A | 100 | 100 | 200 | |
| Nennspannung | kV | 27 | 38 | 27 | |
| Minimum Short Circuit Current | |||||
| - Symmetrisch | kA | 8 | 5 | 7.1 | |
| - Asymmetrisch | kA | 12 | 8 | 10 | |
| Mindestisolationsstufe: | |||||
| - Impulse withstand voltage (BIL), phase to ground and between phases. | kV | 150 | 170 | 150 | |
| - Withstand voltage at power frequency between phases, dry, 1 min. | kV | 60 | 80 | 60 | |
| - Withstand voltage at power frequency between phase and ground, in wet, 10s. | kV | 50 | 70 | 50 | |
| Insulating porcelain material of the base with high purity alumina compositions (between 94% to 99%) with the addition of vitrifiers. | Ja | Ja | Ja | ||
| Minimum creepage distance (Phase-Earth) | mm | 470 | 660 | 432 | |
| Kontaktmaterial | Silver electrolytic copper | Silver electrolytic copper | Silver electrolytic copper | ||
| - Minimum thickness of the top contact silver layer (tab) | µm | 15 | 15 | 15 | |
| - Maximum electrical contact resistance between each terminal and the nearest metal part accessible after contact | Ohm | 0.000099 | 0.000099 | 0.000099 | |
| - Upper contact pressure spring with fastening and alignment mechanism | Stainless steel, grade 304 according to AISI 304, DIN 1.4301 | Stainless steel, grade 304 according to AISI 304, DIN 1.4301 | Stainless steel according to AISI 304, DIN 1.4301 | ||
| Anschlussmaterial | Verzinntes Kupfer | Verzinntes Kupfer | Verzinntes Kupfer | ||
| -Conductor Range (Diameter) | mm | 4.11-11.35 | 4.11-11.35 | 4.11-11.35 | |
| -Terminals for use with copper or aluminum conductors | Ja | Ja | Ja | ||
| -Typ der Terminals | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | Parallel slots, must include bolt, nuts and pressure washers made of stainless steel | ||
| Top support channel material | Galvanized structural steel | Galvanized structural steel | Galvanized structural steel | ||
| - Galvanized Material Standard | ASTM A575 | ASTM A575 | ASTM A575 | ||
| - Verzinkungsstandard | ASTM A153 | ASTM A153 | ASTM A153 | ||
| - Minimum average thickness | µm | 86 | 86 | 86 | |
| Minimaler Öffnungswinkel | 120° | 120° | 120° | ||
| Minimum number of mechanical operations guaranteed | Nein. | 200 | 200 | 200 | |
| Minimum mechanical resistance of the horn for load operation | daN | 200 | 200 | 200 | |
| Dimensions (See Figure 1) | |||||
| L | mm | 704 | 842 | 704 | |
| M | mm | 409 | 431 | 409 | |
| N | mm | 476 | 567 | 476 | |
| P | mm | 72 | 82 | 72 | |
| Q | mm | 131 | 147 | 131 | |
2 | SICHERUNGSHALTERROHR | ||||
| Funktionen | |||||
| - Standard | ANSI/IEEE C 37.40/41/42 | ANSI/IEEE C 37.40/41/42 | ANSI/IEEE C 37.40/41/42 | ||
| - Nennspannung | kV | 27 | 38 | 27 | |
| - Nennstrom | A | 100 | 100 | 200 | |
| - Minimum symmetrical/asymmetrical short-circuit current | kA | 8/12 | 5/8 | 7.1/10 | |
| - Internal diameter range | |||||
| - Minimum | mm | 11.1 | 11.1 | 17.5 | |
| - maximal | mm | 18 | 18 | 23 | |
| - Length (allowable range) | mm | 375±3 | 466±3 | 375±3 | |
| - Metal parts of joining with the base | Bronzeguss | Bronzeguss | Bronzeguss | ||
| - Fuse holder tube cover (top contact) | Silver electrolytic copper, with a minimum thickness of 8 um | Silver electrolytic copper, with a minimum thickness of 8 µm | Silver electrolytic copper, with a minimum thickness of 8 µm | ||
| - Eye hook for pole operation | Cast Bronze, with minimum mechanical resistance of 200daN | Cast Bronze, with minimum mechanical resistance of 200daN | Cast Bronze, with minimum mechanical resistance of 200daN | ||
| - Fuse holder tube material. | Fiberglass with internal coating in moisture-proof vulcanized fiber | Fiberglass with internal coating in moisture-proof vulcanized fiber | Fiberglass with internal coating in moisture-proof vulcanized fiber | ||
| - Fuse holder opening and closing mechanism (fuse holder base) | to avoid fuse holder tube un-alignment greater than 15mm | to avoid holder tube un-alignment no more than 15mm | to avoid fuse holder tube un-alignment no more than 15mm | ||
| Suitable for chicote fuses with removable head (Arc shortening rod) | Ja | Ja | Ja | ||
3 | BEFESTIGUNGSZUBEHÖR | ||||
| - Art der Fixierung | Type B, according to ANSI/IEEE C37.42 | Type B, according to ANSI/IEEE C37.42 | Type B, according to ANSI/IEEE C37.42 | ||
| - Material | Verzinkter Stahl | Verzinkter Stahl | Verzinkter Stahl | ||
| - Materialstandard | ASTM A575 | ASTM A575 | ASTM A575 | ||
| - Verzinkungsstandard | ASTM A153 | ASTM A153 | ASTM A153 | ||
| - Minimum average thickness | µm | 86 | 86 | 86 |
Produktdetailbilder:

Verwandter Produktführer:
With our excellent administration, potent technical capability and strict top quality control technique, we go on to provide our consumers with trusted quality, reasonable price ranges and fantastic providers. We intention at becoming one among your most trusted partners and earning your fulfillment forChina OEM Prepayment system Suppliers –Silver Electrolytic Copper Expulsion Fuse – Holley, The product will supply to all over the world, such as: Singapore, Madras, America, Our faith is to be honest first, so we just supply high quality products to our customers. Really hope that we can be business partners. We believe that we can establish long time business relationship with each other. You can contact us freely for more information and pricelist of our products !